Product overview
HD AFFF 3FZ-C6 Low Temperature Foam is an aqueous film-forming foam concentrate for hydrocarbon fire protection. The manufacturer specifies a 3% solution with compatible water and foam equipment. The selected concentrate, proportioner and discharge device must be checked as a complete system. The freeze-protected formulation has a published −18°C pour point; complete-system suitability at low temperature must still be confirmed.
Technical specifications
| Manufacturer | HD FIRE PROTECT |
|---|---|
| Product / system | AFFF 3FZ-C6 Low Temperature Foam |
| Product type | Foam Systems |
| Product family | Foam Concentrates |
| Subcategory | Foam Concentrates |
| Concentrate type | Freeze-protected AFFF, C6 formulation |
| Mixing ratio | 3% |
| Water compatibility | Fresh / sea-salt / hard water |
| Specific gravity at 20°C | 1.02 ± 0.02 |
| pH at 20°C | 8.0 ± 1.0 |
| Viscosity at 20°C | Less than 10 cSt |
| Pour point | Flows at −18°C |
| Typical expansion | More than 7; equipment and system conditions apply |
| Typical 25% drainage | More than 2 minutes 15 seconds; equipment and system conditions apply |
| Manufacturer-listed approvals | UL Listed to UL 162 |
| Low-temperature selection | Concentrate rating does not replace validation of the water supply and complete system at the intended temperature |
Approval scope applies to the listed system and component configuration. Confirm the selected equipment against the current manufacturer document and project submittal.
Key features
- Concentrate type: Freeze-protected AFFF, C6 formulation
- Mixing ratio: 3%
- Water compatibility: Fresh / sea-salt / hard water
Applications
Class B hydrocarbon hazards such as fuel storage, process areas, refineries, terminals and aviation-fuel facilities within the approved application scope.
Selection and project integration
Share the system drawings, protected hazard, equipment schedule and project specification with UDCT. Product selection should establish the required flow and pressure, pipework connections, materials, installation orientation and compatible components. Check the precise approval scope for the selected model, size and configuration against the current manufacturer documentation.
The product reference does not replace hydraulic calculations or the approved system design. For foam equipment, confirm the concentrate, proportioning range and discharge-device compatibility as one system. Use the manufacturer instructions for installation, commissioning and maintenance, and confirm the supplied configuration with UDCT before procurement.