Product overview
HD AR-AFFF 1X3-C6 is an alcohol-resistant foam concentrate with separate application requirements for hydrocarbon and water-miscible polar-solvent hazards. The manufacturer specifies 1% for hydrocarbons and 3% for polar solvents. Its physical properties and proportioning compatibility should be considered together with the selected discharge equipment, application rate and approved system configuration.
Technical specifications
| Manufacturer | HD FIRE PROTECT |
|---|---|
| Product / system | AR-AFFF 1X3-C6 |
| Product type | Foam Systems |
| Product family | Foam Concentrates |
| Subcategory | Foam Concentrates |
| Concentrate type | Alcohol-resistant AFFF, C6 formulation |
| Hydrocarbon mixing ratio | 1% |
| Polar-solvent mixing ratio | 3% |
| Water compatibility | Fresh / sea-salt / hard water |
| Appearance | Amber viscous liquid |
| Specific gravity at 20°C | 1.02 ± 0.02 |
| pH at 20°C | 8.0 ± 1.0 |
| Viscosity at 20°C | 1,400 ± 200 cPs; spindle 4, 60 rpm |
| Pour point | Flows at 0°C; freeze-protected type separately selected |
| Typical expansion | More than 7; equipment and system conditions apply |
| Typical 25% drainage | More than 5 minutes 30 seconds; equipment and system conditions apply |
| Manufacturer-listed approvals | UL Listed to UL 162 |
Approval scope applies to the listed system and component configuration. Confirm the selected equipment against the current manufacturer document and project submittal.
Key features
- Concentrate type: Alcohol-resistant AFFF, C6 formulation
- Hydrocarbon mixing ratio: 1%
- Polar-solvent mixing ratio: 3%
Applications
Hydrocarbon and compatible polar-solvent hazards in industrial storage, processing and transfer applications, using the formulation-specific concentration and manufacturer design criteria.
Selection and project integration
Share the system drawings, protected hazard, equipment schedule and project specification with UDCT. Product selection should establish the required flow and pressure, pipework connections, materials, installation orientation and compatible components. Check the precise approval scope for the selected model, size and configuration against the current manufacturer documentation.
The product reference does not replace hydraulic calculations or the approved system design. For foam equipment, confirm the concentrate, proportioning range and discharge-device compatibility as one system. Use the manufacturer instructions for installation, commissioning and maintenance, and confirm the supplied configuration with UDCT before procurement.
Manufacturer documents
Official product reference
View this product on the manufacturer website (opens in a new tab)