Product overview
The VES VF5013 and VF5014 are analogue photoelectric duct smoke-sensing arrangements for compatible HVAC and fire alarm integration. Sampling tubes bring duct air to the sensing chamber, with tube selection depending on duct width. The VF5014 adds relay functions and requires an auxiliary 24 V DC supply. Select the unit, sampling arrangement and control interface as part of the approved air-handling and fire alarm design.
Technical specifications
| Brand / product range | VES |
|---|---|
| Product / system | VF5013 / VF5014 Analog Duct Sensors |
| Product type | Fire Detection |
| Product family | Fire Detection & Alarm |
| Subcategory | Addressable Initiating Devices |
| Models | VF5013-00 / VF5014-00 with relays |
| Application | Photoelectric duct smoke detection for compatible HVAC / fire alarm integration |
| Operating loop voltage | 17–41 V DC |
| Average SLC current | VF5013: 2 mA / VF5014: 10 mA |
| Alarm current | VF5013: 8 mA / VF5014: 55 mA, as stated in sheet |
| Auxiliary supply | 24 V DC required for VF5014 |
| Relay arrangement | VF5013: no relay contacts / VF5014: two independently controlled contacts |
| Air velocity | 300–4,000 ft per minute |
| Operating temperature | 32°F to 120°F |
| Humidity | 10–85%, non-condensing |
| Sampling tube choices | VF5003: 3 ft / VF5004: 5 ft / VF5005: 10 ft; select to suit duct width |
| Remote indication | VF5013: alarm / VF5014: alarm and pilot |
| Contact-rating note | The referenced sheet gives inconsistent relay ratings; obtain confirmed model-specific rating before load selection |
| Manufacturer-listed approvals | UL 268A, compatible detector and panel configuration applies |
Approval scope applies to the listed system and component configuration. Confirm the selected equipment against the current manufacturer document and project submittal.
Key features
- Models: VF5013-00 / VF5014-00 with relays
- Application: Photoelectric duct smoke detection for compatible HVAC / fire alarm integration
- Operating loop voltage: 17–41 V DC
Applications
Smoke monitoring in commercial, industrial and residential HVAC ducts within the documented air-velocity range. Duct sensing supports the approved air-handling control strategy and does not replace required open-area detection.
Selection and project integration
Share the fire alarm drawings, equipment schedule, compatible panel platform and cause-and-effect requirements with UDCT. Selection should confirm device protocols, supported interfaces, circuit supervision, power and standby calculations, and the exact enclosure or module arrangement.
Use the current manufacturer documentation to check compatibility, wiring limits, software requirements and approval scope. Commissioning should verify the configured alarm, fault, indication and control functions as part of the complete system. Remote reporting also requires a compatible receiving service and confirmation of local network availability.