The VK506 is a K22.4 ESFR pendent sprinkler for selected palletized, solid-pile and open-rack storage layouts. Viking requires the approval charts and commodity-specific design criteria to be followed. The model is a fast-response pendent sprinkler with a maximum working pressure of 175 psi (12 bar). Product selection must follow Viking's current technical data sheet, approved storage configuration, water supply and the authority having jurisdiction.
Technical specifications
| Manufacturer | The Viking Corporation |
|---|---|
| Brand / product range | VIKING |
| Product / system | VK506 ESFR Pendent Sprinkler |
| Product type | Sprinklers & Valves |
| Product family | Storage Sprinklers |
| Subcategory | Early Suppression Fast Response (ESFR) |
| Model | VK506 |
| Nominal K-factor | 22.4 (320 metric) |
| Manufacturer part numbers | 18493, 18494 |
| Response | Fast (ESFR) |
| Orientation | Pendent |
| Operating element | Fusible element |
| Maximum working pressure | 175 psi (12 bar) |
| Connection | 1 in NPT (25 mm BSP) |
| Application class | Storage, subject to listed design criteria |
Key features
- Early Suppression Fast Response performance for listed storage hazards
- Model-specific 22.4 (320 metric) nominal K-factor
- Manufacturer technical data and approval information available for project submittal
Applications
Engineered warehouse and high-piled storage fire protection. Commodity, storage height, ceiling height, clearance, aisle layout and water demand must be checked against the model-specific Viking data sheet and the relevant listing.
Selection and project integration
Specify model VK506, the required temperature rating and finish, sprinkler orientation, water supply, storage geometry and authority requirements. Do not substitute another ESFR model by K-factor alone; verify the current manufacturer data sheet and approved design criteria before ordering.
Manufacturer documents
Official product reference